CISA Advises C-More EA9 Update for Crafted Project Files
Quick Answer
Update affected engineering workstations to C-More EA9 V6.81, restrict untrusted project-file intake, and validate projects and communications before returning the workstation to service.
Confirm Scope And Apply The Supported Remediation
What to do now: Record exact product and software versions, engineering or control-system owners, network access paths, management restrictions and recovery arrangements. C-More EA9 Programming Software V6.80 and earlier. An attacker must persuade a user to open a crafted project file. Install V6.81 from the official AutomationDirect software channel; restrict project files to trusted sources while rollout is pending. Verify the effective version or interim access controls, test representative operational workflows with the system owner, and retain configuration, change and recovery evidence.
Last verified: 2026-11-24 UTC. Recheck the authoritative advisory and supported distribution channel before changing production.
Scope And Authority
| Product scope | C-More EA9 Programming Software |
|---|---|
| Advisory | ICSA-26-328-01 |
| CVE | CVE-2026-127280 |
| Authoritative release date | 2026-11-24T12:00:00Z — CISA web publication timestamp; the accompanying CSAF initial release is 2026-11-24T06:00:00Z. |
| Authority revision date | No separate revision is stated. |
| Affected versions | C-More EA9 Programming Software V6.80 and earlier. An attacker must persuade a user to open a crafted project file. |
| Fixed version | C-More EA9 Programming Software V6.81. |
| CVSS base score | 7.8 (CVSS v3.1; CISA advisory) |
| CVSS severity | High |
| Exploitation status | CISA reports no known public exploitation specifically targeting this vulnerability.; no exploitation claim is inferred. |
What Changed
CISA published a heap-buffer-overflow advisory for crafted C-More EA9 project files. Opening an attacker-supplied file can corrupt memory, crash the engineering application and potentially execute code. This is a programming-workstation issue with required user interaction.
What To Validate Now
- Inventory. Record exact product and software versions, engineering or control-system owners, network access paths, management restrictions and recovery arrangements.
- Establish applicability. C-More EA9 Programming Software V6.80 and earlier. An attacker must persuade a user to open a crafted project file.
- Remediate. Install V6.81 from the official AutomationDirect software channel; restrict project files to trusted sources while rollout is pending.
- Validate. Verify the effective version or interim access controls, test representative operational workflows with the system owner, and retain configuration, change and recovery evidence.
- Retain evidence. Preserve asset and owner identifiers, the applicability decision, before-and-after versions, change approval, installation output, validation results, and any exception or rollback record.
Operational Cautions
Back up project files and validate compatibility before deployment. Do not infer that a controller firmware update is required from this programming-software advisory. CISA also publishes CVSS v4.0 8.4 High; 7.8 here is its v3.1 base score.
Evidence To Retain
- Exact product, release stream, package or application version, enabled feature, environment, and accountable owner.
- UTC timestamps, authority revision, approved change record, installer or package-manager output, and resulting version.
- Relevant logs and monitoring evidence, test results, exceptions, compensating controls, and rollback decisions.
Related TechGeeks Resources
Authoritative References
Correction policy: If the authority changes affected versions, fixed versions, severity, exploitation information, mitigations, or required action, TechGeeks will update this notice and its verification date.