Johnson Controls Releases EasyIO Neo Firmware and Hardware Fixes

P2 — VALIDATE AND UPDATESEVERITY: SOURCE RATINGS DIFFEREXPLOITATION: NOT STATED

Quick Answer

EasyIO Neo EC V3.3b62/b63 and CW V3.3b24/b25 require attention to both firmware and hardware. EC V3.3b64 and CW V3.3b26 address the firmware findings. For the SWD debug-interface findings in JCI-PSA-2026-19, Johnson Controls considers replacement with the revised hardware remediated; installing the same firmware number on old hardware does not remove physical pins.

Confirm Scope And Apply The Supported Fix

What to do now: Inventory Johnson Controls EasyIO Neo Series EC and CW controllers, match the exact affected release or feature, apply the authority-supported fixed build or service remediation, validate the dependent workflow, and preserve evidence.

Open the authoritative advisory

Last verified: 2026-10-02 UTC. Recheck the authoritative advisory and supported distribution channel before changing production.

Scope And Authority

Product scopeJohnson Controls EasyIO Neo Series EC and CW controllers
AdvisoryJCI-PSA-2026-19 / JCI-PSA-2026-20 / JCI-PSA-2026-30 / ICSA-26-274-04 / ICSA-26-274-05
CVEsCVE-2026-34493, CVE-2026-34494, CVE-2026-64892, CVE-2026-64893
Authoritative release date2026-10-01 (authority date; no vendor time stated; CISA publication 06:00 UTC)
Authority revision dateInitial publication; no later material revision stated when verified
Affected versionsEasyIO Neo EC V3.3b62 and V3.3b63, and EasyIO Neo CW V3.3b24 and V3.3b25.
Fixed versionEC firmware V3.3b64 / CW firmware V3.3b26, plus revised hardware with SWD debug pins removed for the physical-debug findings
CVSS base scoreCISA v3.1: 3.5 for CVE-2026-64892 and 5.4 for CVE-2026-64893. JCI v4.0: 5.9 for CVE-2026-34493/34494 and 5.5 for CVE-2026-64893. JCI-PSA-2026-20 labels CVE-2026-64892 High but supplies no numeric score and an incomplete vector.
CVSS severityCISA Low/Medium; JCI Medium for PSA 19/30 and High for PSA 20. Do not combine different scoring systems into one unqualified range.
Exploitation statusJohnson Controls and CISA do not report known public exploitation; no exploitation claim is inferred.

What Changed

PSA 19 covers physical debug-interface tampering, PSA 20 sensitive-information exposure, and PSA 30 cleartext credentials/session data. PSA 30 disables HTTP by default in the fixed firmware. The vendor PSA 19 physical-access description also differs from its published network attack-vector field; the practical hardware replacement requirement remains explicit.

What To Validate Now

  1. Inventory. Locate Johnson Controls EasyIO Neo Series EC and CW controllers deployments, versions, enabled features, exposure paths, owners, and dependent services.
  2. Establish applicability. Match controller family, hardware revision, and exact EC or CW firmware. Do not treat firmware alone as resolving a finding that requires revised hardware.
  3. Remediate. Deploy EC V3.3b64 or CW V3.3b26 through the supported channel, confirm revised hardware for the SWD findings, disable HTTP, enforce HTTPS/TLS, restrict physical and management access, and follow Johnson Controls hardening guidance.
  4. Validate. Record controller family, actual hardware revision and firmware separately. Have facilities staff verify controller logic and normal HVAC/lighting sequences. Check management access uses HTTPS and that HTTP is disabled as intended; do not assume a default is effective on a migrated configuration. Protect packet captures because they may contain credentials.
  5. Retain evidence. Preserve asset and owner identifiers, the applicability decision, before-and-after versions, change approval, installation output, validation results, and any exception or rollback record.

Operational Cautions

Back up logic/configuration and schedule firmware or hardware work with facilities and safety owners. Obtain vendor confirmation of the replacement hardware; do not probe, remove pins or modify a live controller to test applicability. Source severity differences and the incomplete PSA 20 vector remain unresolved, not independent lab findings.

Evidence To Retain

  • Exact product, release stream, package or application version, enabled feature, environment, and accountable owner.
  • UTC timestamps, authority revision, approved change record, installer or package-manager output, and resulting version.
  • Relevant logs and monitoring evidence, test results, exceptions, compensating controls, and rollback decisions.